DETAILED SUMMARY NDC MEDAN NDC BATAM NDC PALEMBANG NDC JAKARTA NDC SURABAYA NDC BALI
TOTAL NUMBER OF RACK 30 Racks 51 Racks 30 Racks 292 Racks 30 Racks 46 Racks
ADDITIONAL RACK PLAN 2020 : +10 Racks 2020 : +290 Racks
2022 : +200 Racks
2020 : +10 Racks 2020 : +906 Racks
2022 : +1.570 Racks
2024 : +1.570 Racks
2020 : +50 Racks 2020 : +24 Racks
RACK SPECIFICATION 19” Close Rack 42U, 1150mm Depth with Black perforated doors 19” Close Rack 42U, 1150mm Depth with Black perforated doors 19” Close Rack 42U, 1150mm Depth with Black perforated doors 19” Close Rack 42U, 1150mm Depth with Black perforated doors 19” Close Rack 42U, 1150mm Depth with Black perforated doors 19” Close Rack 42U, 1150mm Depth with Black perforated doors
DC Area (Sq Mtrs) Land Area : 470 M2
Building Area : 453 M2 (2 Floor)
Land Area : 6351 M2
Building Area : 1312 M2
Land Area : 468 M2
Building Area : 405 M2 (2 Floor)
Land Area : 3015 M2
Building Area : 2571,87 M2 (4 Floor)
Land Area : 866 M2
Building Area : 449,25 M2 (2 Floor)
Land Area : 645 M2
Building Area : 534 M2 (2 Floor)
DC CLASSIFICATION RATED 2 DESIGN
(99,74%)

(99,98%)
RATED 2 DESIGN
(99,74%)

(99,98%)
RATED 2 DESIGN
(99,74%)
RATED 2 DESIGN
(99,74%)
SLA STANDARD (Zero Downtime Achievement Record) - Network : 99.95%
- Power : 100%
- Network : 99.99%
- Power : 100%
- Network : 99.95%
- Power : 100%
- Network : 99.99%
- Power : 100%
- Network : 99.95%
- Power : 100%
- Network : 99.95%
- Power : 100%
BUILDING MANAGEMENT & DCIM (DATA CENTER INFRASTRUCUTRE MANAGEMENT) REAL TIME DASHBOARD REAL TIME DASHBOARD REAL TIME DASHBOARD REAL TIME DASHBOARD REAL TIME DASHBOARD REAL TIME DASHBOARD
BACKUP SYSTEM (DUAL MMR, POWER, COOLING, NETWORK, PATH) Full Support
(N+1)
Full Support
(N+1)
Full Support
(N+1)
Full Support
(N+1)
Full Support
(N+1)
Full Support
(N+1)
SEPARATED POWER CORD AND DATA CABLE TRAY YES YES YES YES YES YES
FLOOR LOADING & PERFORATED FLOOR PANEL Floor Loading 700 Kg/Sqm,
height 40 Cm
Floor Loading 700 Kg/Sqm,
height 60 Cm
Floor Loading 700 Kg/Sqm,
height 40 Cm
Floor Loading 700 Kg/Sqm,
height 60 Cm
Floor Loading 700 Kg/Sqm,
height 40 Cm
Floor Loading 700 Kg/Sqm,
height 40 Cm
CAPACITY POWER / RACK 220 Volt/2,2 Kw/rack
Up to 4 Kw / rack
220 Volt/2,2 Kw/rack
Up to 6 Kw / rack
220 Volt/2,2 Kw/rack
Up to 4 Kw / rack
220 Volt/2,2 Kw/rack
Up to 6 Kw / rack
220 Volt/2,2 Kw/rack
Up to 4 Kw / rack
220 Volt/2,2 Kw/rack
Up to 6 Kw / rack
COOLING CAPACITY 3 X 20 Kw 6 x 40 Kw 3 x 20 Kw 4 x 80 Kw
13 x 35 Kw
3 x 20 Kw 5 x 35 Kw
PLN PLATINUM SERVICE
(Dual Source From PLN)

(Dual Source From PLN)
Single Source PLN
(Dual Source From PLN)

(Dual Source From PLN)
Single Source PLN
MAIN POWER (PLN ) 105 KVA 555 KVA 164 KVA 1.110 KVA 105 KVA 164 KVA
GENSET 2 x 80 KVA 2 x 500 KVA 1 x 180 KVA 2 x 800 KVA 2 x 80 KVA 1 x 200 KVA
FUEL (TIA-942 min. standard = 72 Jam) Daily tank 2 x 200 L
Main tank 2 x 1.000 L
Max. running 120 hrs
Daily tank 2 x 1.000 L
Main tank 1 x 7.000 L
Max. running 100 hrs
Daily tank 1 x 400 L
Main tank 1 x 1.000 L
Max. running 90 hrs
Daily tank 2 x 1.000 L
Main tank 2 X 12.000 L
Max. running 140 hrs
Daily tank 1 x 200 L
Main tank 2 X 1.000 L
Max. running 120 hrs
Daily tank 1 x 480 L
Main tank 2 X 3.000 L
Max. running 100 hrs
UPS AND BATTERY CAPACITY 1 x 80 KVA
Up to 160 KVA
back up time 15 Mnt
(80 % Load)
2 x 120 KVA
back up time 30 Mnt
(80 % Load)
1 x 96 kVA
Up to 160 KVA
back up time 15 Mnt
(80 % Load)
2 x 200 KVA
4 x 250 KVA
1 x 80 KVA
Up to 160 KVA
back up time 15 Mnt
(80 % Load)
2 x 150 KVA
Back up time 30 Mnt
(80 % Load)
WALL 2 hrs fire rated wall 2 hrs fire rated wall 2 hrs fire rated wall 2 hrs fire rated wall 2 hrs fire rated wall 2 hrs fire rated wall
FIRE SUPPRESSION FM-200 FM-200 FM-200 FM-200 FM-200 FM-200
MULTI LAYER PHYSICAL ACCESS
NETWORK OPERATION CENTER 7 days / 24 hours 7 days / 24 hours 7 days / 24 hours 7 days / 24 hours 7 days / 24 hours 7 days / 24 hours